Rf = 1/Ufouled − 1/Uclean — thermal resistance added by fouling deposits. Calculates fouling factor from measured U values, or predicts fouled U from a known Rf and clean U.
Heat Transfer · HX Design · FoulingSolve for:
Uclean — measured before fouling develops
Ufouled — measured after deposit formation
Compare measured Rf against TEMA standard (optional):
Fouling resistance definition:
Where fouling fits in the overall U formula:
TEMA standard fouling factors (m²·K/W):
| Service | Rf [m²·K/W] |
|---|---|
| Steam / treated cooling water | 0.0001 |
| Seawater (below 52 °C) | 0.0001 |
| City / treated water | 0.0002 |
| River water | 0.0003 |
| Hard water | 0.0006 |
| Crude oil (mild) | 0.0003 – 0.0005 |
| Fuel oil / residuals | 0.0009 |
TEMA factors are conservative design margins for clean fluid at normal operating temperatures. Actual fouling at a given service time may differ significantly.